True on-line, double-conversion UPS provides pure, full-time sine wave AC output free of surges, voltage fluctuations and line noise
12,000VA/8400W output power capacity with dual voltage output of 208/120V or 240/120V
4U high power density power module and 4U external battery pack support rackmount installation in 8 rack spaces (8U)
Dual conversion UPS actively converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection
Hardwire input and output terminals are mounted on a detachable backplate with manual bypass switch to enable hot-swappable UPS replacement without powering off connected equipment
Hot-swappable modular rack/tower UPS system offers 12,000VA on-line, double-conversion UPS support for server, network and telecommunications equipment. Maintains battery-derived AC output during blackouts with active, full-time power conditioning. Fault-tolerant auto-bypass prevents unexpected service interruptions during overload or internal fault conditions. 4U power module and 4U external battery pack installs in 8 rack spaces (8U). Upright tower installation supported with optional accessories. Maintains full-time sine wave output within 3% of selectable 208/120 or 240/120V AC. Corrects brownouts and overvoltages from 65V to 140V (L-N). Expandable runtime with optional external battery packs. Converts raw input from AC to DC, then resynthesizes output power back to perfect sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. Network-grade AC surge and noise suppression. Network management interfaces include combination DB9 RS-232 enabled and dry contact serial port, enhanced USB port and SNMPWEBCARD slot.
True on-line, double-conversion UPS provides pure, full-time sine wave AC output free of surges, voltage fluctuations and line noise
12,000VA/8400W output power capacity with dual voltage output of 208/120V or 240/120V
4U high power density power module and 4U external battery pack support rackmount installation in 8 rack spaces (8U)
Dual conversion UPS actively converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection
Hardwire input and output terminals are mounted on a detachable backplate with manual bypass switch to enable hot-swappable UPS replacement without powering off connected equipment
Provides perfectly regulated, sine wave output power free of line noise, transient surges and frequency variation for the most efficient operation of critical servers, networking and telecommunications equipment
Maintains output within 3% of selected 208/120V or 240/120V nominal voltage during brownouts and overvoltages
Supports connected equipment during blackouts for 20/7 minutes at half/full load levels
Some external battery configurations require the use of Tripp Lite's external battery configuration software
Network interfaces support simultaneous communications via DB9 port, USB port and SNMPWEBCARD slot
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP
Built-in emergency power off (EPO) interface with cable
Split phase, four-conductor hardwire input connection on included detachable PDU
Warranty - Yes
Rackmountable - Yes
UL Rated - Yes
Spec Sheet available - Yes
Output volt amp capacity:
12000 VA
Output kVA Capacity:
12 kVA
Output Watt Capacity:
8400 W
Output power factor:
0.7
Nominal Output Voltages Supported:
120, 208, 240 V
Frequency Compatibility:
60 Hz
Output voltage regulation (line mode):
+/-3 %
Output voltage regulation (Economy line mode):
+/-10 %