A double rack-space unit, the SEQ features two always-on receptacles and four programmable banks. There are three physical banks of four receptacles each and a fourth ‘virtual’ bank for controlling remote units, allowing for infinitely expanding power distribution schemes.The SEQ has an LCD display on the front panel that provides unit status, AC line voltage and is also used in programming the unit. Settings are saved in nonvolatile memory. The SEQ can control other SurgeX products, or several SEQs can be interconnected to operate together. With many powerful features, the SEQ is extremely easy to install, program and use.The unit features both common mode and normal mode Impedance Tolerant EMI/RFI filtering, SurgeX ICE -Inrush Current Elimination and COUVS -Catastrophic Over/Under Voltage Shutdown for a complete power conditioning solution. SurgeX Advanced Series Mode technology is superior to conventional MOV circuitry or MOV-Hybrid designs and is completely non-sacrificial. Our zero let-through technology provides the most reliable protection available. It stops all surges up to 6,000 volts (unlimited surge current) without producing harmful side effects such as ground contamination or common-mode disturbances.
Magnetic shielding steel enclosure
9ft grounded 3-wire #12 line cord
Three sequenced banks of four receptacles with combined load of 20 amperes
Two receptacles always on
Control output for fourth external bank
Can be used to control other SurgeX surge eliminators and power conditioners, or daisy-chained with other SEQs
Easy setup and programming
LCD display
Setup stored in nonvolatile memory
Provides continual display of AC line voltage
Accommodates any type of control input
DC voltage or contact closure feedback to
Crestron, AMX or similar control devices.
Output to drive up to four status LEDs
Advanced Series Mode surge protection
COUVS catastrophic over/under-voltage shutdown
SurgeX ICE inrush current elimination technology
Advanced Impedance Tolerant EMI/RFI filtering
Thermal circuit breaker overload protection
10-year warranty
Made in USA
Warranty - Yes
UL Rated - Yes
Spec Sheet available - Yes
Operating Temperature (Maximum):
95 F
Operating Temperature (Minimum):
41 F
Cord Length (in/mm):
108 in
Current Rating:
20 Amps
Number of Outlets:
12
UL Rated:
Yes
AC Voltage:
120 Volts
Current Draw:
20 Amps
Depth:
10.50 in
Height:
3.50 in
Width:
19 in
Product Weight:
16 lbs
Warranty (Length/Type):
10 Year
Power Requirement (no load):
20 Watts
UL 1449 Adjunct Classification Test Results:
1000 surges, 6000 volts, 3000 amps, B3 pulse, measured suppressed voltage 170 volts, no failures
Federal Guidelines:
Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz:
EMI/RFI Filter, Common Mode (50-ohm load): 18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz: